| Parameter | Details |
|---|---|
| Manufacturer | Omron |
| Part Number | NT10S-SF122 |
| Product Type | Programmable Terminal / Interactive Display (HMI) |
| Series | NT10S |
| Power Supply Voltage | 24 VDC-1 |
| Power Consumption | 6 W (max)-1 |
| Display Type | Interactive operator panel (Non-touch, text-based)-1-4 |
| Backlight | CFL (Cold Fluorescent Lamp) |
| Function Keys | 4 function keys (F1 - F4) + System keys-1-5 |
| Communication Interface | RS-232C, RS-422, RS-485 (Host Link)-2 |
| Programming Method | NT Support Tool (requires screen data transfer)-5 |
| Mounting | Panel-mounted-1 |
| Terminal Block Screw Size | M3.5-2 |
| Recommended Crimp Terminal Hole Size | M3.5-2 |
| Applicable Wire Size (Stranded) | 1.04 to 2.63 mm²-2 |
| Front Panel Protection | IP65 (dust-tight, protected against water jets) |
| Operating Temperature | 0°C to 50°C |
| Storage Temperature | -20°C to 60°C |
| Operating Humidity | 35% to 85% RH (non-condensing) |
| Weight | Approx. 650 g |
Basic HMI Operation: The NT10S-SF122 is a compact operator interface terminal designed for straightforward machine interaction, monitoring, and equipment control in industrial automation environments-1.
User Interface: Features 4 function keys (F1-F4) that can be programmed for specific operations. An initial "TOOL MODE" can be accessed by pressing the F4 key during startup for communication with the Support Tool-5.
Integration: Compatible with Omron Sysmac automation platforms and Programmable Controllers (PLCs) via Host Link communication. The terminal block provides connections for 24 VDC power, FG (Frame Ground), and RS-485 communication lines-2-4.
Durable Construction: Built with an industrial-grade, IP65-rated front panel, resistant to vibration and dust, making it suitable for harsh factory environments-1.
Compact Design: Its small footprint and low power consumption (6W) make it ideal for applications where panel space is limited-1.
| Terminal Label | Description |
|---|---|
| 24 VDC | +24V DC Power Supply Input |
| FG | Frame Ground (for noise protection) |
| RS-485 | Communication line to Programmable Controller |